Operating Instructions

Operating Instructions
Transponder-Coded Safety Switch CTP-AR
18
(translation of the original operating instructions) 2123041-07-05/19
10.4. Requirements for connection cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection cables.
Ì Use connection components and connection cables from EUCHNER
Ì On the usage of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connection cables:
For safety switches CTP-…-AR-…-SAB-… with plug connectors 2xM12
Parameter Value Unit
Conductor cross-section, min. 0.25 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type LIYY 8x0.25mm² or 5x0.34mm²
For safety switches CTP-…-AR-…-SH-… with plug connector M23 (RC18)
Parameter Value Unit
Conductor cross-section, min. 0.25 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
Recommended cable type
LIFY11Y min. 19-core