Operating Instructions
13
2123041-07-05/19 (translation of the original operating instructions)
Operating Instructions
Transponder-Coded Safety Switch CTP-AR
EN
7.4. Wire front release
Release via a pull wire. Depending on the type of attachment, the wire front release can be used as emergency unlocking
or escape release.
The following applies to non-latching wire front releases.
If the release is to be used as emergency unlocking, one of the following measures must be
taken (see EN ISO 14119:2013, section 5.7.5.3):
Ì Install the release so that it can be reset only with the aid of a tool.
Ì Alternatively, the reset can be undertaken at the control system level. E.g. by means of a
plausibility check (status of the safety outputs does not match the guard locking activation
signal).
The emergency-unlocking specications in chapter 7.2 on Page 12 apply irrespective of
this information.
Important!
Ì The wire front release meets the requirements of CategoryB accord-
ing to ENISO13849-1:2015.
Ì The correct function depends on the laying of the pull wire and on the
attachment of the pull handle, and this is the responsibility of the plant
manufacturer.
Ì The actuator must not be under tensile stress during manual release.
7.4.1. Laying wire front release
Important!
Ì Loss of the release function due to mounting errors, damage or wear.
Ì Check the release function every time after mounting.
Ì When routing the wire front release, ensure that it operates smoothly.
Ì Observe the min. bending radius (100mm) and minimize the number of bends.
Ì The switch is not allowed to be opened.
Ì Observe the notes on the enclosed data sheets.