Owner manual

Operation MODEL 2081 TURNTABLE SERIES
20 © ETS-LINDGREN L.P. – JANUARY 2003
REV D – PN 399212
ALTIVAR MOTOR BASE CONFIGURATION
The following settings are the defaults for the Altivar motor base
set by ETS-Lindgren:
Altivar
Setting
208/230 VAC 60 Hz 400 VAC 50 Hz
bFr 60 50
ACC
0.1 0.1
dEC
0.1 0.1
LSP 0 0
HSP 75 75
UnS 230 400
FrS 60 60
tFr
90 90
Should you need to change the configuration on the Altivar motor
base supplied with your turntable the Altivar manual is available at
www.SquareD.com.