Technical data

IZMX circuit-breakers, INX switch-disconnectors
Minimum clearances
CA01305001Z-EN www.eaton.com
97
Minimum clearances
Recommended safety clearances
The following information about safety distances is intended to provide a guideline for the installation of circuit-breakers in an enclosure.
Recommended enclosure clearance and ventilation
The illustration shows a typical enclosure.
The table below lists the associated minimum distances between enclosures and ventilation openings.
This information is intended as a guideline for constructing a suitable circuit-breaker enclosure. Ensure the integration complies with IEC 61439.
Cell switch (optional)
Locking facilities (optional)
Ventilation openings (do not cover!)
Enclosure clearance To insulated surface To grounded metal surface With cell switch or locking
facilities
mm mm mm
Withdrawable units a
b
0
25
0
25
0
25/75
Fixed mounted a
b
150
30
250
70
Width c Width of cassette + 75 mm
Height d 550 mm
Depth e 450 mm (front control panel bay)
Ventilation
holes
160 cm
2
(800 - 3200 A)
320 cm
2
(4000 A)
Top or rear vent
Rear or lower vent
100
b
b
b
a
a
a
c
e
d
d
e
c
Top and bottom