Technical data

82 IZMX circuit-breakers, INX switch-disconnectors
IZMX circuit-breakers
CA01305001Z-EN www.eaton.com CA01305001Z-EN www.eaton.com
IZMX circuit-breakers, INX switch-disconnectors
IZMX circuit-breakers
RES820...
IZMX40N...20...
RES825...
IZMX40N...25...
RES832...
IZMX40N...32...
RES840...
IZMX40N...40...
RESC08...
IZMX40H...08...
RESC10…
IZMX40H...10...
RESC13…
IZMX40H...12...
RESC16…
IZMX40H...16...
RESC20…
IZMX40H...20...
RESC25…
IZMX40H...25...
RESC32…
IZMX40H...32...
RESC40…
IZMX40H...40...
General
Standards IEC/EN 60947 IEC/EN 60947
Ambient temperature Storage °C -25 - +70 (device with LCD-display -20 - +70) -25 - +70 (device with LCD-display -20 - +70)
Operating (open) °C -25 - +70 (device with LCD-display -20 - +70) -25 - +70 (device with LCD-display -20 - +70)
Mounting position
Utilization category B B B B B B B B B B B B
Protection type IP20, IP55 with protective cover, IP41 with door
sealing frame
IP20, IP55 with protective cover, IP41 with door sealing frame
Direction of incoming supply as required as required as required as required as required as required as required as required as required as required as required as required
Main conducting paths
Rated current = rated uninterrupted current I
n
= I
u
A 2000 2500 3200 4000 800 1000 1250 1600 2000 2500 3200 4000
Rated uninterrupted current at 50 °C
1)
I
u
A 2000 2500 3200 4000
2)
800 1000 1250 1600 2000 2500 3200 4000
2)
Rated uninterrupted current at 60 °C
1)
I
u
A 2000 2500 3200 3650
2)
800 1000 1250 1600 2000 2500 3200 3650
2)
Rated uninterrupted current at 70 °C
1)
I
u
A 2000 2280 3200 3500
2)
800 1000 1250 1600 2000 2500 3200 3500
2)
Rated impulse withstand voltage U
imp
V AC 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000 8000
Rated operational voltage, max. Ue V DC 690 690 690 690 690 690 690 690 690 690 690 690
Use in IT electrical power networks up to U = 440 V I
IT
kA 50 50 50 50 50 50 50 50 50 50 50 50
Overvoltage category/pollution degree III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3 III/3
Rated insulation voltage U
i
V 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
Switching capacity
Rated short-circuit making capacity
up to 440 V 50/60 Hz I
cm
kA 166 166 166 166 231 231 231 231 231 231 231 231
Rated short-time withstand current 50/60 Hz
t = 1 s I
cw
kA 85 85 85 85 85 85 85 85 85 85 85 85
Rated short-circuit breaking capacity I
cn
IEC/EN 60947 operating
sequence I
cu
O-t-CO
up to 240 V 50/60 Hz I
cu
kA 85 85 85 85
up to 440 V 50/60 Hz I
cu
kA 85 85 85 85 105 105 105 105 105 105 105 105
up to 690 V 50/60 Hz I
cu
kA 75 75 75 75
up to 1100 V 50/60 Hz I
cu
kA
IEC/EN 60947 operating
sequence I
cs
O-t-CO-t-CO
up to 240 V 50/60 Hz I
cs
kA 85 85 85 85
up to 440 V 50/60 Hz I
cs
kA 85 85 85 85 105 105 105 105 105 105 105 105
up to 690 V 50/60 Hz I
cs
kA 75 75 75 75
up to 1100 V 50/60 Hz I
cs
kA
Operating times for ON ms 30 30 30 30 30 30 30 30 30 30 30 30
Total closing time ms 35 35 35 35 35 35 35 35 35 35 35 35
Operating times for OFF
Total opening time with shunt releases ms 22 22 22 22 22 22 22 22 22 22 22 22
Total opening time with undervoltage releases ms 37 37 37 37 37 37 37 37 37 37 37 37
Total trippinig time (until fault is fully cleared) ms 45 45 45 45 45 45 45 45 45 45 45 45
Maximum operating frequency Operations/h 60 60 60 60 60 60 60 60 60 60 60 60
Heat dissipation at rated current I
n
Fixed mounting W 285 300 480 750 90 90 135 225 285 300 480 750
Withdrawable units W 345 450 720 1120 135 120 180 300 345 450 720 1120
Weight
Fixed mounting 3-pole kg 45 45 45 45 45 45 45 45 45 45 45 45
4-pole kg 56 56 56 56 56 56 56 56 56 56 56 56
Withdrawable 3-pole kg 69 69 69 69 69 69 69 69 69 69 69 69
(CB only) 4-pole kg 86 86 86 86 86 86 86 86 86 86 86 86
Cassette 3 pole kg 29 29 29 29 29 29 29 29 29 29 29 29
4 pole kg 35 35 35 35 35 35 35 35 35 35 35 35
Notes
1)
Permissible continuous current for circuit-breakers operating in switchboards at various internal ambient temperatures.
The switchboard’s internal ambient temperature should be estimated using the calculation methods of IEC regulation.
2)
Rated continuous current stated applies only with 4 x 120 x 10 mm vertical terminal rails painted black.
The values are reduced by 100 A each with 4 x 100 x 10 mm.
30˚ 30˚
30˚ 30˚
30˚ 30˚
30˚ 30˚
83
IZMX40… IZMX40…