Technical data

6 IZMX circuit-breakers, INX switch-disconnectors
Electronic releases
CA01305001Z-EN www.eaton.com
Electronic releases
Standard protection Standard plus
selectivity
Universal
protection
Professional
protection
Type Coding
Digitrip 520 LI
IZMX-DTA
Digitrip 520 LSI
IZMX-DTV
Digitrip 520M LSI
IZMX-DTU
Digitrip 1150i LSI
IZMX-DTP
Current Range
200 - 4000 A 200 - 4000 A 200 - 4000 A 200 - 4000 A
RMS Value Monitoring
Protective functions
General
Ordering options LI LSI; LSIG LSI; LSIG; LSIA LSI; LSIG
Rating plug (I
n
)
Overtemperature trip
Overload protection L
Overload trip I
r
(0.5 - 1.0) x I
n
(0.5 - 1.0) x I
n
(0.5 - 1.0) x I
n
(0.5 - 1.0) x I
n
Long delay time at 6 x I
r
(I
2
t Curve) t
r
2 - 24 s 2 - 24 s 2 - 24 s 2 - 24 s
Long delay time at 6 x I
r
(I
4
t Curve) t
r
1 - 5 s
IEC Type A, B, C curves
High load alarm
2)
Off, 0.5 - 1.0 x I
r
Thermal memory (enable / disable)
Short-time delayed
Short-circuit protection
S
Short delayed pickup short-circuit protection I
SD
(2 - 10) x I
r
(2 - 10) x I
r
(2 - 10) x I
r
Short delay time at 8 x I
r
(I
2
t Curve) t
SD
100 - 500 ms 100 - 500 ms 100 - 500 ms
Short delay time, flat characteristic curve t
SD
100 - 500 ms 100 - 500 ms 100 - 500 ms
Zone selectivity ZSI
Non-delayed short-circuit protection I
Non-delayed short-circuit protection (2 - 12) x I
n
(2 - 12) x I
n
(2 - 12) x I
n
(2 - 12) x I
n
Switch-off function
Closing releases MCR
Optional ground fault protection G
Ground/Earth fault alarm A
1)
1)
Ground/Earth fault protection release Ig (0.25 - 1.0) x I
n
3)
(0.25 - 1.0) x I
n
3)
(0.24 - 1.0) x I
n
Short delay time at 0.625 x I
n
(I
2
t curve) tg 100 - 500 ms 100 - 500 ms 100 - 500 ms
Short delay time, flat characteristic curve tg
100 - 500 ms 100 - 500 ms 100 - 500 ms
Zone selectivity ZSI
Thermal memory
Disable ground fault protection
Neutral protection N
Notes l
n
= rating plug (rate current module) = rated operational current transformer
l
r
= Set value overload trip (= rated operational current of system)
1)
Requires external 24 V DC control voltage supply.
2)
High load alarm available only on LSI styles, active at 85% of I
r
3)
Limited to 1200 A
4)
Hand-held kits available for basic verification or advanced testing
5)
Captures fault current of latest event when control power is supplied
Standard
Optional
– not available
IZMX16, INX16, IZMX40, INX40