Datasheet
Thermal-Magnetic Circuit Breaker 2210-T2..
www.e-t-a.de
1912
 1
 1
Description
Typical applications
One, two and three pole thermal-magnetic circuit breakers with trip-free 
mechanism and toggle actuation (S-type TM CBE to EN 60934/IEC 934). 
Featuring a combi-foot design for both symmetric and asymmetric rail 
mounting. Available with auxiliary contact (1 x N/O or 1 x N/C) for status 
signalling. Two and three pole models are internally linked to ensure that 
both/all poles trip in the event of an overload on one pole, even if the 
actuator is held in the ON position. This CBE can be supplied in current 
ratings up to 32 A with a choice of characteristic curves. All screw 
terminals are recessed for safety. Approved to CBE standard EN 60934 
(IEC 60934).
Process control equipment, robotics, machine tool control,
communications systems, instrumentation.
2210-T2..
2-pole
Features  Your benefits
l  Comprehensive approvals allow global use
l  Current rating range from 0.1 A to 32 A 
l  Very small width of only 12.5 mm including auxiliary contacts
l  High vibration resistance to DNV GL Class B for mounting with 
  combustion engines, pumps, compressors 
l  Compliant with the relevant requirements of the railway   
  standards DIN EN 50155, DIN EN 61373 and EN 45545  
  (detailed information upon request)
l  Space and weight savings of at least 50 % compared to 
  conventional MCBs
l  Reduced assembly times thanks to integral auxiliary contacts
l  Optimum equipment protection through fine grading of   
  current ratings
Preferred types – for more details on all configurations please see order numbering code 
Preferred types are E-T-A products most frequently used by E-T-A 
customers. We manufacture E-T-A preferred types in particularly high 
volumes. Our preferred types are supplied at shorter lead times than 
non-standard versions.
Preferred types Standard current ratings (A)
1-pole 0.5 1 2 3 4 5 6 8 10 16 20
2210-T210-K0M1-H121-
x x x x x  x x x x x x
2-pole 0.5 1 2 3 4 5 6 8 10 16 20
2210-T220-K0M1-H221-
x x  x x x x
For access to the latest documents please follow:www.e-t-a.de/en053
Data sheetApprovals
Compliances