Datasheet
Thermal-Magnetic Circuit Breaker 2210-T2..Thermal-Magnetic Circuit Breaker 2210-T2..
www.e-t-a.de
1912
6
1
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section
Technical information.
Multi pole devices: all poles symmetrically loaded. With single pole overload,
thermal tripping will be at max. 1.7 x I
N
with curves F1, F2 and M1.
1)
Magnetic tripping currents are increased by 30 % on DC supplies
(curves F2, M1).
Ambient °F
temp. °C
-22
-30
-4
-20
+14
-10
+32
0
+73.4
+23
+86
+30
+104
+40
+122
+50
+140
+60
Derating factor
0.76 0.79 0.83 0.88 1 1.04 1.11 1.19 1.29
… times rated current
Trip time in seconds
… times rated current
0.001
0.001
12468102040
10000
1000
100
10
1
0.1
0.01
0.001
6080100
124681020
40
10000
1000
100
10
1
0.1
0.01
6080100
12468102040
10000
1000
100
10
1
0.1
0.01
6080100
Trip time in seconds
Trip time in seconds
-M1 0.1…6 A AC/DC
1)
-T1 0.1…6 A AC only
-M1 8…32 A AC/DC
1)
-T1 8…32 A AC only
… times rated current
… times rated current
Trip time in seconds
0.001
12468102040
10000
1000
100
10
1
0.1
0.01
6080100
23 °C
60 °C
-30 °C
Typical time/current characteristics