Datasheet
Thermal Overcurrent Circuit Breaker 1658-...
www.e-t-a.de
 1
 1
1908
Description
Typical applications
Ordering information
Technical data
Very cost effective design to meet international requirements. No 
exposed  metal parts which are, or could become, current-carrying 
except for terminals. R-type TO CBE to EN 60934.
l  Manual reset, cycling trip free mechanism
l  Extremely small and lightweight
l  UL, CSA, VDE and EN 60934 (IEC 60934) approved
Battery chargers, consumer products, power supplies, motors.
1658-...
Standard current ratings and typical voltage drop values
Type No.
1658  single pole thermal circuit breaker
  Threadneck design
  G21 manual reset type, 3/8“-27 threadneck
  A00 auto reset type, without threadneck 
   Hardware
   00  no hardware
   01 one PAL nut Y306 671 01, bulk
   02   one PAL nut Y306 671 01,  
one knurled nut Y307 117 02, bulk
    Terminals
    P10  blade terminals A6.3-0.8 (QC .250)
    P13  blade terminals A6.3-0.8 (QC .250), 90°
    Current ratings
    5 ...30 A
1658 - G21 - 02 -  P10 - 5 A Ordering example
* Screws and lock washers bulk shipped
Packaging unit: minimum order quantity 250 pieces
Current
rating (A)
voltage drop 
values (mV)
Current
rating (A)
voltage drop 
values (mV)
5 ≤ 250 12 ≤ 250
6 ≤ 250 15 ≤ 250
7 ≤ 250 16 ≤ 250
8 ≤ 250 20 ≤ 250
9 ≤ 250 25 ≤ 250
10 ≤ 250 30 ≤ 250
Preferred types Standard current ratings (A)
5 6 7 8 9 10 12 15 16 20 25 30
1658-G21-02-P10-
x x x x x  x x x x x x x
1658-G21-02-P13-
x x x x x x x x x
1658-A00-00-P10-
x x x x x x x x x
Preferred types
For further details please see chapter: Technical Information 
Voltage rating  AC 240 V; DC 28 V 
Current ratings  5...30 A 
Typical life 
  AC + DC  5...16 A  1,000 operations at 2 x I
N
, inductive
    17...25 A  1,000 operations at 2 x I
N
, resistive
Ambient temperature  -20...+60 °C (-4...+140 °F), 
    ≤ 7 A max. +40 °C (+104 °F)
Insulation co-ordination  rated impulse  pollution
(IEC 60664 and 60664 A)  withstand voltage degree
   2.5 kV 2
    reinforced insulation in operating area
Dielectric strength 
(IEC 60664 and 60664A) test voltage
  operating area  AC 3,000 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
  5...7 A  180 A
    8...30 A  200 A
Interrupting capacity  I
N
  U
N
(UL 1077/EN 60934 PC1)  5...16 A  AC 240 V  1 000 A, C, 1
    5...30 A  AC 125 V  2 000 A, C, 1
    5...30 A  DC 32 V  2 000 A, C, 1
    5...30 A  AC 125 V  2 000 A, C, 1 
      DC 28 V  (1658-A...)
Degree of protection  operating area IP40 
(IEC 60529/DIN 40050)  terminal area IP00
Vibration  8 g (57-500 Hz) ± 0.61 mm (10-57 Hz),
    to IEC 60068-2-6, test Fc, 
    10 frequency cycles/axis
Shock  30 g (11 ms)
    to IEC 60068-2-27, test Ea
Corrosion  96 hours at 5 % salt mist,
  to IEC 60068-2-11, test Ka
Humidity  240 hours at 95 % RH
    to IEC 60068-2-78, test Cab
Mass  approx. 16 g
Behaviour at rated 
switching capacity 
(EN 60934; 
test sequence D)
operat. I
N
U
N
40 5...16 A AC 240 V 6 x I
N
 ind
40 5...16 A DC 28 V 4 x I
N
 ind
40 17...25 A AC 240 V 120 A 
resistive
40 17...25 A DC 28 V 120 A 
resistive