user manual
– 7 – ETAsys.com
Specifications are subject to change without notice.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800-321-6699 • Fax: 800-996-3821
ETA-S20
AC Power Distribution Unit & Surge Suppressor
INSTALLATION
Beforeinstalling,westronglysuggestyoureadtheentiremanualtoensureyoubenetfromallthefeaturesoftheETA-S20.The
ETA-S20 can be placed on a shelf or rack mounted in a standard 19" width rack. When rack mounted, placement within the rack is
exiblehowevertheETA-S20shouldbewithin6'ofadedicated20AACoutlet.Whenrackmounting,useRackRailtypescrewswhich
are
10
⁄32" x 1". Always make sure the 20A outlet is properly inspected by a certified electrician prior to connecting the ETA-S20. Make sure
to inspect the equipment that is to be plugged into the ETA-S20 to ensure it does not exceed 20A total amperage draw.
SPECIFICATIONS
Type AC Power Distribution & Surge Suppressor
Front Panel
Outlets 20ANEMA5-20R,1Unswitched
ActivationSwitch Rocker,IlluminatesRedwhenintheONposition
CircuitBreaker 20AResettable
Indicators ACPowerONRed,ACProtectActiveONGreen
Rear Panel
ACOutlets NEMA5-20R,8Outletstotal:7Switched,1Unswitched
ACMainsPowerCord 9'(2.74m),12gauge,ACPlugNEMA5-20P
Technical Data
Current Rating Limited to 16A 2000W Continuous
CurrentProtection 20AACMainsBreaker
OperatingVoltage 102VAC–132VAC
MOV-NewGeneration Qty.3HottoNeutral,HottoGround,NeutraltoGround
ClampingVoltage L-N:400,L-G:500,N-G:400/3KA,8/20µs
Max.SpikeClampingVoltage 6KV,1.2/50µs
Max. Spike Clamping Resp. Time <1 nanosecond
MaximumSurgeCurrent 45000A,8/20µs
EnergyRating 900Joules,8/20µs
NoiseAttenuationEMI/FRI 40dB@10kHz-100MHz
TemperatureRange 5°–35°C
Humidity Range 5% to 95% R.H.
Mechanical
ChassisFinish Black
Mounting Rack Mount, 1 RU
Height 1.75" (1RU, 44.5mm)
Width 19" (482.6mm)
Depth 3.75" (95.5mm)
Weight 5.5 lbs (2.49kg)
Power Consumption 800 milliwatts
Agency Listings UL and cUL Listed