TECHNICAL DATA
Current Rating 15 amps
Operating Voltage 102 - 132VAC
High Voltage Surge Protection Trigger at 133VAC, 1ms Typically
Low Voltage Protection Trigger 101VAC, 1ms Typically
Voltmeter Accuracy ±1.5VAC
Spike Protection Modes DCS(DualClampingSuppression)CircuitryonincomingACMainsandEachSequential
Section Output
Min. Spike Clamping Voltage 460VRMS@3,000A
Max. Spike Clamping Voltage 6000V
Max. Spike Clamping Resp. Time 1 nanosecond
Spike Clamping Voltage @ 100A 1250Vp for 20µs
Maximum surge current 6,500A
Energy Rating @ 2ms 2000 Joules
Noise Attenuation EMI/RFI
Seq. Section 1 & 2 10dB@10kHz
40dB@100kHz
100dB@10MHz
Temperature Range 5° to 35°
C
Humidity Range 5%to95%R.H.
Power Consumption 12 Watts
MECHANICAL
Chassis Finish Black
Mounting Rack Mount, 19", 1RU
DIMENSIONS
Height 1.75" (1RU, 45mm)
Width 19" (216mm)
Depth 8.5" (549mm)
Weight 7.6lbs (3.45kg)
Agency Listings MET(UL1449Code)
ETA-ECS3