Specifications

– 13 – ETAsys.com
Specifications are subject to change without notice.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800-321-6699 • Fax: 800-996-3821
TECHNICAL DATA
Current Rating 15 amps
Operating Voltage 102 - 132VAC
High Voltage Surge Protection Trigger at 133VAC, 1ms Typically
Low Voltage Protection Trigger 101VAC, 1ms Typically
Voltmeter Accuracy ±1.5VAC
Spike Protection Modes DCS(DualClampingSuppression)CircuitryonincomingACMainsandEachSequential
Section Output
Min. Spike Clamping Voltage 460VRMS@3,000A
Max. Spike Clamping Voltage 6000V
Max. Spike Clamping Resp. Time 1 nanosecond
Spike Clamping Voltage @ 100A 1250Vp for 20µs
Maximum surge current 6,500A
Energy Rating @ 2ms 2000 Joules
Noise Attenuation EMI/RFI
Seq. Section 1 & 2 10dB@10kHz
40dB@100kHz
100dB@10MHz
Temperature Range 5° to 35°
C
Humidity Range 5%to95%R.H.
Power Consumption 12 Watts
MECHANICAL
Chassis Finish Black
Mounting Rack Mount, 19", 1RU
DIMENSIONS
Height 1.75" (1RU, 45mm)
Width 19" (216mm)
Depth 8.5" (549mm)
Weight 7.6lbs (3.45kg)
Agency Listings MET(UL1449Code)
ETA-ECS3
Power Sequencer & Conditioner