Specifications

– 7 – ETAsys.com
Specifications are subject to change without notice.
1601 Jack McKay Blvd. • Ennis, Texas 75119 U.S.A.
Telephone: 800-321-6699 • Fax: 800-996-3821
ETA-20SH
AC Power Conditioning & Suppression Module
FRONT PANEL
1.Trigger/StatusPortPinIdentification
All signals are of low voltage and current. DO NOT MISS WIRE or damage may occur.
A. (+) requires a minimum of 5–24V DC to activate the module with 5mA of current. Note: The DCV can be supplied from any
source. The EVS protection requires the ETA-ECS6RM for operation.
B. G=CircuitGround.MustbeofthesamecircuitastheDCVsource.
C. V=ACVoltageStatusSignal.ReportstheIncomingACMainsVoltagetotheECMmodulebacktotheETA-ECS6RM.
D. A=ACCurrentStatusSignal.ReportstheACMainsCurrentDrawtotheECMmodulebacktotheETA-ECS6RM.Note: Not
available with the ETA-ECM20.
E. D=FaultStatusSignal.ReportsanyfaultconditionsofanECMmoduletotheETA-ECS6RM.
2.ExternalTrigger/ManualOnSwitch
The ETA-20SH has a manual override switch allowing it to be used as a local Conditioner and Spike Suppressor. For remote monitoring
and activation, the switch must be in the “External Trigger” position.
3.ActiveLED
This LED will illuminate Green when the ECM module has sensed the proper DCV to activate the unit. Note: If connected to the
ETA-ECS6RM and the EVS circuit has been activated, this LED will not be lit. The Channel Status LED on the ETA-ECS6RM will flash
indicating a problem and the ECM module will not turn On until the AC Mains voltage is stable.
4.ACFaultLED
If damage to the Spike Suppression circuit occurs, this LED will illuminate Red. This LED will not turn Off until repaired.
5.IncomingACLED
This LED will illuminate Red when the ECM has incoming AC power present at the module. This LED must be On to operate.
Note:IfthisLEDisnotilluminatingcheckthefollowing:1)theunitispluggedin,2)theACMainsBreakerfeedingtheAClegtothe
ECM module is Off, 3) the internal fuse has been damaged. This should only be inspected by an authorized technician.
6.ACMainsOutlet
Two 120V AC 20A outlets.
7.ACMainsPowerCord
9'(3m),12-gauge.
1 25
3
7