Certifications

4-pole, 16A and less, 250V ac and less, 65V dc and less. Series TMC protectors have been
investigated for motor overcurrent protection.
Note: Suffix letters and/or numbers added to series designation indicate type of construction and
special features.
Supplementary Protectors, Series 1180, 0.1 to 10A, 250V ac, 72V dc, 1-pole.
Cat. No. 2216, thermal magnetic supplementary protectors for general Industrial use, single pole or two poles,
277Vac, 50/60Hz, 0.1 to 16A; single pole, 50Vdc, 0.1 to 16A; two poles, 80Vdc, 0.1 to 16A (two poles break),
with manually switch on and off function, with or without auxiliary contacts.
Auxiliary contact is rated 1A at 277Vac and 50Vdc.
Application code:
Trip current (TC): TC1. (135 % of marked ampere rating)
Overload Ratings (OL):
Voltage rating poles Current ratings OL code
277 V ac 1, 2 0.1 L 10 A OL1
277V ac 1, 2 12 L 16A OL0
50 V dc
1
0.1 L 16 A OL1
80 V dc
2
0.1 L 10 A OL1
80 V dc
2
12 L 16A OL0
Short Circuit Ratings (SC):
Voltage rating poles Current ratings Short Circuit Rating
277 V ac
1
0.1 L 16A 1000A, C1
277V ac
2
0.1 L 16A 1000A, C1
50 V dc
1
0.1 L 16 A 1000A, C1
80 V dc
2
0.1 L 16 A 1000A, C1
Notes:
1. These devices are accepted as components for use only in other Certified equipment where the suitability of
the combination is determined by CSA Group.
2. Rating of series fuse approx. 4 times current rating of protector, but not less than 15A.
3. ManufacturerLs specified minimum Trip Current: 135 % of marked ampere rating.
4. Enclosure size for temperature rise test: 13 x 4 x 18 cm.
5. The terminals are intended to be factory wired only and the suitability of connection
(including spacings) shall be determined in accordance with the requirements
of the end-use application.
6. These devices are not suitable for use as branch circuit protection.
7. These device may optionally be provided with socket 80PLUS-PT01 or 81PLUS-UT01
for field wiring.
/ka
Seite
6
von
6
Cert.Record No 016186_0_000, Class No 3215 30, DQD No 557 Rev.2003
-
05
-
15
09.
10.
2014
...