Data Sheet
REX12 Electronic Circuit ProtectorREX12 Electronic Circuit Protector
www.e-t-a.de
12
1830
4
Accessories
view: X
view: X
view: X
view: X
PM12-T01-00-LOAD-20A
contact via connector arm
contact via connector arm
PM12-T01-00-LOAD-20A potential module – LOAD
(10-way, 1 x supply, 9 x LOAD)
PM12-T02-00-LOAD-20A potential module – LOAD
(2 x 5-way, 1 x supply and 4 x LOAD each)
Schematic diagram
PM12-T02-00-LOAD-20A
Schematic diagram
Potential Module
PM12-T01-00-LOAD-20A
DC 24 V
80
PM12-T01
-00-LOAD
DC 24 V
20 A
LOAD+
ADDR
COM
0 V
LINE+1
2.5
2.4
2.3
2.2
2.1
max. 10 A / terminal
2.10
2.9
2.8
2.7
2.6
80
12.5
12.5
View without connector arm
G ERMANY
G ERMANY
Potential Module
PM12-T02-00-LOAD-20A
DC24 V
2.1 2.6
2.2 2.7
2.3 2.8
2.4 2.9
2.5 2.10
LOAD+
2.1 2.6
2.2 2.7
2.3 2.8
2.4 2.9
2.5 2.10
ADDR
COM
0 V
LINE+1
2.5
2.4
2.3
2.2
2.1
max. 10 A / terminal
2.10
2.9
2.8
2.7
2.6
max.10 Amax.10 A
PM12-T02
-00-LOAD
DC 24 V
20 A
LOAD+
2.1 2.6
2.2 2.7
2.3 2.8
2.4 2.9
2.5 2.10
LOAD+
2.1 2.6
2.2 2.7
2.3 2.8
2.4 2.9
2.5 2.10
contact via connector arm
contact via connector arm
View without connector arm
Technical data
Please observe general data of REX / EM / PM
Operating voltage U
B
DC 24 V (18...30 V)
Operating current I
B
max. load 20 A
Insulation co-ordination 0.8 kV / pollution degree 2
Screw terminals LOAD+
Push-in terminal PT 2.5 0.14 mm
2
... 2.5 mm
2
flexible
AWG24 – AWG14 rigid
stripping length 8 mm ... 10 mm
Dimensions (w x h x d) 12.5 x 80 x 98 mm
Mass approx. 52 g
Approvals UL 1059, File # E335289
Technical data
Please observe general data of REX / EM / PM
Operating voltage U
B
DC 24 V (18...30 V)
Operating current I
B
max. load 20 A
Insulation co-ordination 0.8 kV / pollution degree 2
Screw terminals LOAD+
Push-in terminal PT 2.5 0.14 mm
2
... 2.5 mm
2
flexible
AWG24 – AWG14 rigid
stripping length 8 mm ... 10 mm
Dimensions (w x h x d) 12.5 x 80 x 98 mm
Mass approx. 52 g
Approvals UL 1059, File # E335289