User`s manual

APPENDIX D
SOFTWARE COMMANDS
APX D-4
HELP
HELP switches are:
HELP Displays this Help menu.
HELP ALL Displays All commands switches and
arguments.
HELP CHANGE Displays only the commands that were change
on the last SAVE.
HELP CONTROL Displays Control commands switches and
arguments.
HELP PLC Displays PLC commands switches and
arguments.
HELP RADIO Displays Radio commands switches and
arguments.
HELP RS-232 Displays RS232 commands switches and
arguments.
HELP SETUP Displays Setup commands switches and
arguments.
HELP SYSTEM Displays System commands switches and
arguments.
IDLECont (on/off)
This command enables the idle port disconnect timer. This means
that if enabled the idle port will be disconnected from the
CONVERSE or TRANSPARENT MODE and returned to
COMMAND MODE if the RS-232 port is not active for the length of
time defined by IDLETime command. Factory default = OFF.
IDLEFine (on/off)
Sets the IDLETime unit time intervals.
ON: IDLETime units = tics (1 tic = 16.7ms).
OFF: IDLETime unit = 1 sec.
Factory default = OFF.
IDLETime (1-255)
This command sets the time limit for the idle port disconnect
timer. Factory default = 3O.
JOHNctrl (on/off)
This function enables the Johnson controller protocol. For further
detail Reference the EST Engineering Report on Johnson controller
interfacing.
Factory default = OFF.
LAtfreq (1-2)
This command is only supported on the Model 96. This allows
selection of the desired serial frequency synthesizer on the Tx/Rx
card. A one (1) or two (2) specifies the desired synthesizer to latch
the corresponding divide by "N", divide "A", and the two bit switch
settings.
LINKStat
This command displays the current link status.
MESSForm (on/off)
When enabled all of the system status and error messages will be in
a formatted form.
"xx" indicates what error or message (See Error Messages and
System Status Messages).
nEMxx <CR> [ESTeem Error Messages]
nECxx <CR> [Communication Error Messages]
nSSxx <CR> [System Status Messages]
nSSxx-xxxx <CR> [System Status Message W/Returned Value]
n is the User Definable Prefix character (See Prefix).
Factory default = OFF.
MOdecontr (Hardware/Software)
HARDWARE: The mode of the ESTeem modem is controlled by pin
19 of the RS-232C connector. A low (0) directs the ESTeem into
the COMMAND mode. A high (1) directs the ESTeem into
CONVERSE/TRANSPARENT mode.
SOFTWARE: The mode of the ESTeem modem is controlled by
ASCII character.
Factory default = SOFTWARE
MODEL (xx)
Displays the product model of default firmware that is installed.
Model should be the same as product being used.
MODCTRL (on/off)
This command enables the Modicon controller protocol. For further
detail Reference the EST Engineering Report on Modicon controller
interfacing.
Factory default = OFF.