Instruction manual
5
Essex Electronics, Inc. | 805.684.7601 | 800.KEY-LESS | fax 805.684.0232 | keyless.com
1. Remove power.
2. Jumper the two pins above the connector labeled "CONFIG.”
3. Apply appropriate power. (You should hear 4 beeps and the
RED LED will flash and the GREEN LED will be solid).
4. Once the Keypad is in configuration mode, enter 0099#. The
Keypad will beep twice and both LEDS will flash for approxi-
mately 10 seconds. (During this time, the Keypad will appear
dead. Do NOT remove power!)
5. Once the reset is complete, you will hear 4 beeps and the RED
LED will flash and the GREEN LED will be solid.
6. Enter the configuration number followed by #.
a. Keypad Output
Keypad Output Configuration Site Code
26 Bit Wiegand (default) 1 # 000
8 Bit Word 2 #
BCD 3 #
Serial ASCII 4 #
ABA Track II Clock & Data 5 #
4 Bit Word 6 #
Keypad Reset
In certain cases you may want to erase all user codes and restore
system defaults. To perform this procedure:
CAUTION: This procedure completely erases the memory and
restores factory defaults! Once the memory is cleared, all pro-
grammed User Codes are erased and factory default settings
are restored.