Installation manual
28 Reference & Installation Manual
• The panel will send a fire loop trouble report (if programmed at address 500) to the Monitoring Station.
• A trouble indicator, key [11], and a fire zone indicator, key [3], will flash on the keypad.
• Alarms will generate an intermittent output signal (see Figure below), regardless of the system's current arming status.
• Alarms are always audible, regardless of other settings.
Figure 26
7.5.1 Zone 15 (Enable/Disable)
Feature Select Programming
D
Address 090, key [1]
Default: Zone 15 Enabled
If the ATZ feature is enabled and zone 3 has been set as a fire zone, zone 15 must be disabled if it is not going to be
used.
Key [1] "Off": Zone 15 Enabled
Key [1] "On": Zone 15 Disabled
[
ENTER] + Installer Code + [10] [9] [10] + [1] On/Off + [ENTER]
7.6 Instant Zones
Feature Select Programming
D
Addresses 104 & 106, keys [1] to [12]
Using the "Feature Select Programming Method", select which zones will be defined as Instant Zones. If an "Instant" zone opens,
the control panel will immediately generate an alarm after the "Zone Speed" has elapsed.
7.7 Follow Zones
Feature Select Programming
D
Addresses 108 & 110, keys [1] to [12]
Using the "Feature Select Programming Method", select which zones will be defined as Follow Zones. Follow zones function as
follows:
• If a follow zone opens and no entry delay zones have been triggered; the control panel will immediately generate an alarm
after the zone speed has elapsed.
• If a follow zone opens during another zone's entry delay period, the control panel will wait until the end of the entry delay
period before generating an alarm.
• If a follow zone opens when more than one entry delay zone has been triggered, the panel will wait until the end of the entry
delay zone that opened first before generating an alarm.
7.8 Entry Delay 1
Decimal Programming
D
Address 050
Default: 45 seconds
Any zone that has not been identified as either Instant Zones, Follow Zones, Entry Delay 2, or "24 Hour" & Fire Zones (see
above) will automatically default to Delay 1. You can program the Delay 1 period between 001 and 255 seconds into address
050. If a zone defined as Delay 1 opens in an armed system, the control panel will wait the pre-programmed period before
generating an alarm. This provides the users the time required to disarm the system when entering the protected area.
[
ENTER] + Installer Code + [10] [5] [10] + 3-digit decimal value (001-255) + [ENTER]
7.9 Entry Delay 2
Feature Select Programming
D
Addresses 112 & 114, keys [1] to [12]
Using the "Feature Select Programming Method", select which zones will be defined as Entry Delay 2 Zones. If a zone defined as
Delay 2 opens in an armed system, the control panel will wait the Entry Time Delay 2 (see below) period before generating an
alarm. This provides the users the time required to disarm the system when entering the protected area.