7.1 Zone Speed
Decimal Programming
D
Address 053
Default: 600mS
The zone speed applies to all zones whether the system is armed or disarmed. The zone speed defines how quickly the control
panel will respond to an open zone. The control panel will not display and/or respond to an open zone until the programmed zone
speed elapses. All other zone definitions and options do not come into effect until the zone speed has elapsed.
Example: The system is armed and the zone speed is set for 1.2 seconds. A zone opens and closes in less than 1.2
seconds the control panel will not respond (i.e. no reporting, no alarm and no display on keypad).
The zone speed can be set from 15ms to 3.8s (001 to 255 X 15ms). This feature prevents any momentary glitches in the system
from causing an alarm or unnecessary reporting.
[
ENTER] + Installer Code + [10] [5] [3] + 3 digit decimal value (001-255) + [ENTER]
7.2 Advanced Technology Zoning (ATZ)
Feature Select Programming
D
Address 090, key [8]
Default: ATZ Disabled
Enabling the ATZ feature allows you to install two detection devices per zone input. Each detection device will have its own zone
number and each will transmit a separate alarm code that will display on the keypad. For information on how to connect the
detection devices and how the panel recognizes them, please refer to section 2.10.
Key [8] "Off": ATZ Disabled
Key [8] "On": ATZ Enabled
[
ENTER] + Installer Code + [10] [9] [10] + [8] On/Off + [enter]
7.3 Intellizones
Feature Select Programming
D
Addresses 092 & 094, keys [1] to [12]
If an alarm condition occurs on a zone identified as Intellizone, the control panel will trigger a timer and will not generate an alarm
until one of the following conditions occurs within a specified period (see Intellizone Time Delay below):
An alarm condition occurs on another zone during intellizone time delay.
The zone that is in alarm has restored and re-occurred during intellizone time delay.
The zone that is in alarm remains in alarm the entire intellizone time delay.
Note: Intellizone timer will only begin after the zone speed period has elapsed (see section 7.1).
Do not use the Intellizone feature on zones programmed with any Entry Delay. An alarm may occur when
disarming the system.
7.3.1 Intellizone Time Delay
Decimal Programming - Address 057
Default: 48 seconds
You can set the Intellizone Time Delay between 010 and 255 seconds. Before an Intellizone can generate an alarm,
one of three conditions must occur during this time delay (see section 7.3).
[
ENTER] + Installer Code + [10] [5] [7] + 3-digit decimal value (010-255) + [ENTER]
7.4 Silent Zones
Feature Select Programming
D
Addresses 096 & 098, keys [1] to [12]
Using the "Feature Select Programming Method", select which zones will be defined as Silent Zones. If an alarm occurs on a
Silent Zone, the control panel will report the alarm (see Event Reporting in section 6) to the monitoring station without triggering
any bells and/or sirens. Note if zone 3 is defined as 24 hour (fire zone), the control panel will generate an audible alarm,
overriding a silent zone definition.
7.5 24 Hour & Fire Zones
Feature Select Programming
D
Addresses 100 & 102 , keys [1] to [12]
Using the "Feature Select Programming Method", select which zones will be defined as 24 hour Zones. Keypad zones should
not be programmed as 24hr zones. Regardless of the system’s armed status, an open “24hr” zone will always generate an
alarm.
If zone 3 is defined as "24 hour", it becomes a "Fire Zone". Connect the smoke detectors as described in section 2.11. An open
"Fire Zone" will generate the following: