Repair manual

32
Fault code Cause
Fault Description • Remedial measures
039 Vehicle blower control - short circuit Black 1 mm² cable from the 18-pin control unit connector, compartment
6 to the 8-pin cable harness connector, compartment 7, and from there to
the blower relay has short-circuit.
Check lead and connections and, if necessary, eliminate short circuit.
Check mounting of the relay.
Replace relay.
If the fault could not be eliminated by taking the remedial measures listed
above, then replace control unit.
044 Water pump - relay coil open circuit Check mounting of the relay on the control unit.
045 Water pump - relay coil short circuit Replace relay.
If the fault could not be eliminated by taking the remedial measures listed
above, then replace control unit.
046 Solenoid valve - open circuit "Solenoid valve" cable section from the control unit (connector position “D”)
to the solenoid valve has open circuit or ground leakage.
Check leads and connections to solenoid valve, if necessary eliminate
ground leakage.
Replace solenoid valve coil.
If the fault could not be eliminated by taking the remedial measures listed
above, then replace control unit.
047 Solenoid valve - short circuit “Solenoid valve” cable section from the control unit (connector position “D”)
to the solenoid valve has short-circuit.
Check leads and connections to solenoid valve, if necessary eliminate
short circuit.
Replace solenoid valve coil.
If the fault could not be eliminated by taking the remedial measures listed
above, then replace control unit.
048 Nozzle holder heater - • Check mounting of the relay on the control unit.
relay coil open circuit Replace relay.
049 Nozzle holder heater -
relay coil short circuit
050 Operation disable - control unit is locked The control unit remains locked through 10 attempts at start-up without
flame detection.
Control unit unlocked by clearing the fault memory with modular timer,
diagnostic unit or KD 2000 (see pages 26 to 29).
For remedial measures, see fault code 052.
051 Flame monitor reports • Replace burner.
"Flamme vor Brennstoff" [Flame without fuel]
052 No start or safety time overshoot No flame was detected within the ignition phase.
Check combustion air inlet and exhaust gas piping.
Check fuel supply (supply and return).
Check flame pipe to make sure it is correctly mounted in the heat
exchanger.
Check functioning of the ignition spark generator only with the test unit for
burner head; if necessary, replace the ignition spark generator.
Check ignition electrode, adjust and, if necessary, replace.
Check electric leads and connections.
Check flame monitor for dirt accumulation and, if necessary, clean.
Replace fuel atomizer nozzle.
If the fault could not be eliminated by taking the remedial measures listed
above, then replace control unit.
High voltage
Take care when checking the
ignition spark generator!
4 / Troubleshooting