Repair manual

31
Fault code Cause
Fault Description • Remedial measures
020 Ignition spark generator - open circuit Control line from ignition spark generator to the control unit has open circuit
or short circuit.
Check cable section from the ignition spark generator to the control unit
and, if necessary, eliminate open circuit or short circuit.
Check functioning of the ignition spark generator only with the test unit for
burner head; if necessary ,replace the ignition spark generator.
If the fault could not be eliminated by taking the remedial measures listed
above, --> replace control unit.
021 Ignition spark generator - ground leakage Control line from the ignition spark generator to the control unit has ground
leakage.
Check cable section from the ignition spark generator to the control unit
and, if necessary, eliminate ground leakage.
Check functioning of the ignition spark generator only with the test unit for
burner head; if necessary, replace the ignition spark generator.
If the fault could not be resolved by taking the remedial measures listed
above, --> replace control unit.
025 Diagnostic output - short circuit Blue / white 1 mm² cable from the 18-pin control unit connector,
compartment 12 to the 8-pin cable harness connector, compartment 2 has
short-circuit against +U
B
Check lead and connections and, if necessary, eliminate short circuit.
032 Burner motor does not turn - on start-up Fan wheel is chafing or is blocked.
033 Burner motor does not turn - during operation Burner motor faulty.
Generator voltage too low.
Check that fan wheel is running freely.
Check lines and connections to the burner motor.
Check functioning of the installed burner motor only with the test unit for
burner head; if necessary, replace the burner motor.
If the fault could not be eliminated by taking the remedial measures listed
above, --> replace control unit.
Fuel pump is blocked.
Check that fuel pump is running freely. If necessary, replace the burner.
037 Water pump - fault Check in advance:
Is Bus 2000 water pump installed?
Is Bus 2000 water pump cable section “Diagnosis” connected?
Does the Bus 2000 water pump have any power?
If yes - detach plug connection from the “Diagnosis” cable section.
Start HYDRONIC - if fault code 037 is no longer displayed,
then check the Bus 2000 water pump for dry running
and / or for blockages.
- If fault code 037 continues to be displayed, then apply the
remedial measures described for the water pump (standard
model).
Water pump (normal model) is installed?
If yes - detach plug connection from the “Water pump” cable section,
apply power to the 2-pin connector on the “Water pump”
cable section and check for correct functioning.
If the water pump is functioning OK, then check fuse (15A),
cable section and water pump connections --> if fault code
037 continues to be displayed, then replace the control unit.
High voltage
High voltage
Apply max. 12 V at burner
motor
4 / Troubleshooting