Operating instructions
9
IInnssttaallllaattiioonn PPrroocceedduurreess
FFuueell SSyysstteemm
HYDRONIC 10
*
FUEL
TA N K
3
6
7
4
5
2
2
5
6
MAX. 6’6”
MAX. 2’6”
MAX. 20’
MAX. 6’6”
1
FFuueell SSyysstteemm TToolleerraanncceess
FFuueell LLiinnee
Right Wrong
Bubble
Correct
Wrong
NNoottee::
Butt joints and clamps on all connections.
• Route fuel lines from the fuel pick-up pipe to the heater.
• Use fuel lines provided.
• Other sizes or types of fuel lines may inhibit proper fuel flow.
• Make proper butt joints using clamps and connector pieces
as shown
• Use a sharp utility knife to cut plastic fuel lines to avoid burrs.
NNoottee::
Fuel line limits must not be exceeded.
Ensure that the following conditions are met.
Bottom of the fuel metering pump must be within
a height of 2’6” of the bottom of the fuel pick-up pipe.
Fuel metering pump must be within a total
distance of 6’6” from the fuel pick-up pipe.
Pressure Runs of less than 1.3 mtrs (50”) use
only 3.5mm rubber (360 75 300)
The Hydronic 10 boxed unit is most commonly provided with
the fuel metering pump mounted inside the box. This is to
reduce installation time and to protect the pump from corrosion.
If specifications cannot be met the pump must be mounted
externally. See illustration for connections and specifications. All
parts necessary to do the installation are included in the kit as
shown.
1. Fuel Pick-Up Pipe
2. 11mm Clamp
3. 5.0mm Fuel Line
4. Fuel Metering Pump
5. 9mm Clamp
6. 3.5mm Rubber Connector
7. 2.0mm White Plastic Fuel Line
See notes if length is less
than 1.3 mtr (50”)