Unit installation
32
R6GP-120*-235C
HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
4692
RPM 969
kW
2.75
1.2
CFM
4492
RPM
973
kW
2.61
1.3
CFM
4535 4305
RPM
998 976
kW
2.79 2.52
1.4
CFM
4569
4318 4066
RPM 1022
1001 980
kW
2.92
2.66 2.39
1.5
CFM
4308 4054 3799
RPM
1027 1006 984
kW
2.76 2.49 2.22
1.6
CFM
4368 4084 3797 3510
RPM
1050 1030 1009 988
kW
2.89 2.61 2.34 2.07
1.7
CFM
4422 4120 3817 3493
RPM
1071 1053 1034 1014
kW
3.03 2.74 2.44 2.17
1.8
CFM
4177 3875 3573
RPM
1075 1056 1037
kW
2.89 2.58 2.27
1.9
CFM
4127 3908
3296
RPM
1098 1079
1063
kW
2.96 2.72
2.31
2.0
CFM
4115 3866 3616
RPM
1118 1101 1083
kW
3.01 2.76 2.51
*Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 28. Blower Performance for R6GP-120*-235C Units
(10 Ton Horizontal Models Only)