Unit installation
31
R6GP-120*-235C
HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)
Downfl ow Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
RPM
kW
1.0
CFM
RPM
kW
1.1
CFM
4672
RPM 975
kW
2.65
1.2
CFM
4673
4466
RPM 998
979
kW
2.75
2.50
1.3
CFM
4630
4429 4227
RPM 1018
1000 982
kW
2.90
2.65 2.40
1.4
CFM
4611
4394 4191 3988
RPM 1039
1020 1003 985
kW
2.95
2.70 2.50 2.30
1.5
CFM
4613
4391 4168 3714
3260
RPM 1058
1041 1023 1006
989
kW
3.10
2.85 2.60 2.38
2.15
1.6
CFM
4379 4181 3982
3257
RPM
1061 1046 1031
1012
kW
2.90 2.70 2.50
2.25
1.7
CFM
4480 4233 3976 3718
RPM
1087 1070 1053 1036
kW
3.10 2.80 2.55 2.30
1.8
CFM
4244 3996 3683 3370
RPM
1089 1072 1056 1039
kW
2.90 2.60 2.40 2.20
1.9
CFM
4278 4011 3744
RPM
1111 1093 1075
kW
3.10 2.80 2.50
2.0
CFM
4252 4016 3455
RPM
1130 1115 1097
kW
3.10 2.90 2.50
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 27. Blower Performance for R6GP-120*-235C Units
(10 Ton Downfl ow Models Only)