Unit installation

30
R6GP-090*-200C
HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
1.2
CFM
3524
RPM 1160
kW
2.16
1.3
CFM
3495
3344
RPM 1190
1167
kW
2.30
2.08
1.4
CFM
3491
3339 3186
RPM 1220
1196 1171
kW
2.41
2.17 1.93
1.5
CFM
3545
3316 3137 2958
RPM 1247
1226 1202 1178
kW
2.53
2.27 2.07 1.86
1.6
CFM
3391 3145 2941 2736
RPM
1254 1232 1208 1183
kW
2.37 2.14 1.90 1.66
1.7
CFM
3458
3215 2971 2736
RPM 1282
1260 1237 1214
kW
2.54
2.28 2.01 1.74
1.8
CFM
3538
3273 3016 2758
RPM 1313
1289 1265 1241
kW
2.69
2.39 1.92 1.44
1.9
CFM
3383 3123 2840
RPM
1319 1296 1272
kW
2.55 2.24 1.74
2.0
CFM
3543 3447
3181 2915
RPM 1364 1350
1325 1299
kW
2.87 2.65
2.36 2.07
*Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 26. Blower Performance for R6GP-090*-200C Units
(7.5 Ton Horizontal Models Only)