Unit installation
29
R6GP-090*-200C
HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)
Downfl ow Performance Chart
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
1.2
CFM
3417
3226 3035
RPM 1232
1203 1173
kW
2.32
2.10 1.88
1.3
CFM
3258 3055 2852
RPM
1235 1205 1175
kW
2.15 1.96 1.78
1.4
CFM
3448
3267 3085 2856 2626
RPM 1292
1265 1237 1208 1178
kW
2.47
2.24 2.01 1.82 1.64
1.5
CFM
3300 3099 2898 2677
RPM
1295 1268 1240 1211
kW
2.33 2.10 1.86 1.66
1.6
CFM
3164 2932 2705
RPM
1299 1271 1243
kW
2.24 1.96 1.69
1.7
CFM
3392 3178 2963 2756
RPM
1356 1329 1302 1274
kW
2.63 2.34 2.06 1.80
1.8
CFM
3422 3214 2997
RPM
1384 1358 1332
kW
2.75 2.53 2.26
1.9
CFM
3437 3251 3016
RPM
1414 1389 1364
kW
2.88 2.58 2.42
2.0
CFM
3306 3033
RPM
1419 1394
kW
2.76 2.45
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 25. Blower Performance for R6GP-090*-200C Units
(7.5 Ton Downfl ow Models Only)