Unit installation

24
P6SP-120* & Q6SP-120* & Q5SN-120*
HSD kits:
920395 (208-230V, 3Ø, 60 Hz)
920396 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open ‡
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.9
CFM
4904
4685
RPM 956.5
937
kW
2.81
2.58
1.0
CFM
4914 4717
4520
RPM 980 959
938
kW
2.94
2.7
2.46
1.1
CFM
4738
4527 4317
RPM 982
961 940
kW
2.8
2.57 2.34
1.2
CFM
4784
4561 4317 4073
RPM 1002.5
984 964 944
kW
2.94
2.66 2.43 2.19
1.3
CFM
4568
4378 4125 3871
RPM 1005.5
987 967 946
kW
2.79
2.53 2.29 2.04
1.4
CFM
4558 4352 4147 3897 3647
RPM
1027 1009 990 970 949
kW
2.90 2.65 2.40 2.16 1.93
1.5
CFM
4358 4137 3915 3595
RPM
1030 1012 993 973
kW
2.74 2.50 2.26 2.02
1.6
CFM
4326 4135 3749
3363
RPM
1052 1033 1016
999
kW
2.87 2.60 2.35
2.10
1.7
CFM
4327 4120 3912
3361
RPM
1072 1054 1036
1020
kW
2.96 2.71 2.46
2.20
1.8
CFM
4137 3889 3640
RPM
1074 1057 1040
kW
2.78 2.54 2.29
1.9
CFM
4068 3824
3313
RPM
1096 1077
1063
kW
2.87 2.60
2.26
2.0
CFM
4083 3797 3511
RPM
1118 1099 1080
kW
2.93 2.68 2.42
*Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 20. Blower Performance for P6SP-120*, Q6SP-120*, & Q5SN-120* Units
(10 Ton Horizontal Models Only)