Unit installation
22
P6SP-090*
HSD kits:
920559 (208-230V, 3Ø, 60 Hz)
920558 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open ‡
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
1.2
CFM
RPM
kW
1.3
CFM
3397
3341 3284
RPM 1178
1171 1163
kW
2.34
2.20 2.06
1.4
CFM
3303 3210 3117
RPM
1192 1181 1169
kW
2.24 2.10 1.96
1.5
CFM
3434
3214 3065 2916
RPM 1233
1205 1189 1173
kW
2.44
2.15 2.00 1.85
1.6
CFM
3296 3098 2911 2723
RPM
1241 1217 1197 1177
kW
2.33 2.11 1.90 1.68
1.7
CFM
3406
3168 2929 2717
2505
RPM 1278
1252 1226 1204
1181
kW
2.52
2.27 2.01 1.79
1.57
1.8
CFM
3240 3000 2759
RPM
1285 1258 1231
kW
2.41 2.14 1.87
1.9
CFM
3334 3088 2869
RPM
1316 1289 1266
kW
2.56 2.25 2.00
2.0
CFM
3435
3178 2921
RPM 1347
1321 1294
kW
2.73
2.44 2.15
*Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
†
† These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 18. Blower Performance for P6SP-090* Units
(7.5 Ton Horizontal Models Only)