Unit installation

16
R6GP-072*-100C
MSD kits:
920609 (208-230V, 3Ø, 60 Hz)
920560 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
RPM
kW
0.9
CFM
2618 2403 2188
RPM
975 948 920
kW
1.12 0.98 0.84
1.0
CFM
2577 2367 2073
1865
RPM
1006 980 952
924
kW
1.17 0.99 0.88
0.70
1.1
CFM
2562 2361 2085
RPM
1037 1006 983
kW
1.21 1.07 0.93
1.2
CFM
2575 2328 2085
RPM
1062 1041 1011
kW
1.31 1.10 0.95
1.3
CFM
2601 2356 2048
RPM
1094 1066 1045
kW
1.36 1.18 0.98
1.4
CFM
2580 2357 2126
RPM
1122 1099 1071
kW
1.46 1.25 1.12
1.5
CFM
2569 2323 2129
RPM
1149 1125 1104
kW
1.51 1.33 1.16
1.6
CFM
2307
RPM
1154
kW
1.37
*Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values include losses for: Unit Casing, 2” Disposable Filters, Dry Evaporator Coil & Installed Heat Exchanger
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 12. Blower Performance for R6GP-072* Units
(6 Ton Horizontal Models Only)