Unit installation

14
P6SP-090*
MSD kits:
920607 (208-230V, 3Ø, 60 Hz)
920606 (460V, 3Ø, 60 Hz)
Horizontal Flow Performance Chart*
‡ Indicates Factory Sheave Setting for Pre-confi gured Units
External
Unit Static
(in-Wg)
Operating @
230 or 460
Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2 Turn
Open
1 Turn
Open
1.5 Turns
Open ‡
2.0 Turns
Open
2.5 Turns
Open
3.0 Turns
Open
3.5 Turns
Open
4.0 Turns
Open
4.5 Turns
Open
5.0 Turns
Open
5.5 Turns
Open
6.0 Turns
Open
0.8
CFM
3411
3228 3136 3043
RPM 1053
1025 1013 1000
kW
1.98
1.78 1.68 1.58
0.9
CFM
3309 3131 3005 2878
RPM
1065 1039 1022 1005
kW
1.94 1.75 1.59 1.43
1.0
CFM
3410
3221 3031 2851 2670
RPM 1110
1083 1055 1032 1009
kW
2.07
1.89 1.70 1.54 1.38
1.1
CFM
3321 3114 2906 2681
2455
RPM
1122 1096 1070 1043
1015
kW
2.03 1.84 1.64 1.46
1.27
1.2
CFM
3423
3198 2964 2729
2492
RPM 1162
1132 1103 1074
1046
kW
2.17
1.91 1.56 1.20
1.20
1.3
CFM
3268 3033 2783
2533
RPM
1169 1140 1110
1080
kW
2.12 1.84 1.63
1.41
1.4
CFM
3347 3106 2864 2590
2315
RPM
1203 1174 1145 1115
1085
kW
2.26 2.01 1.75 1.56
1.36
1.5
CFM
3399 3174 2924 2673
RPM
1231 1206 1178 1149
kW
2.37 2.08 1.86 1.63
1.6
CFM
3235 2993
RPM
1236 1210
kW
2.23 1.98
*Requires horizontal conversion kit. Please refer to unit TSL for kit number.
Values includes losses for: Unit Casing, 2” Disposable Filters & Dry Evaporator Coil
Values shown refl ect operation at 230V or 460V. For operation at 208V, deduct 0.025 from unit static.
Deduct 250 Cfm for electric heater kits
3862
Indicates a recommended unit operational point
1159
3.03
3493
Indicates an allowable setting that is not recommended for unit operation
These operational points should be carefully examined by the installer for proper unit setup and heater operation if used.
1017
2.07
Indicates a setting that is not permitted for unit operation
Table 10. Blower Performance for P6SP-090* Units
(7.5 Ton Horizontal Models Only)