Troubleshooting guide

9
TO CHANGE TO 380 V OR 415 V INPUT:
On the main transformer (T1) - both master and slave:
For 415 V input, move the wire from H4 to H3 for all three coils.
For 380 V input, move the wire from H4 to H2 for all three coils.
On the control transformer (T2):
For 415 V input, move the brown wire on H9 to H6.
For 380 V input, move the brown wire on H9 to H5.
Figure 2-2. Master and Slave Configurations