Installation manual
630167_5_Manual_Installation_US_R-emotion
5.2 Non-Combustible Mantle Clearances:
If the entire installation (mantle, wall and cavity) is
constructed from non-combustible materials, the
clearances to mantles may be as shown in the shaded
area.
6.0 Corner Installations:
If a cavity is to be created in a corner,
the following drawing gives the minimum
sizes.
7.0 Laying Gas Pipe:
Gas pipe should be sized as per the requirements of relevant local or national codes. The
pipe sizing must be sufficient to deliver the following volume of gas to the fireplace with all
other gas appliances in the home running at the same time;
ST900 = 19,500 BTU/h max on Natural Gas
High Altitude Installations
When installing this appliance at an elevation above 2000 feet, it may be necessary to decrease the input rating by
changing the existing burner orifice to a smaller size. Input rate should be reduced by 4% for each 1000 feet above a
2000 foot elevation in the U.S.A, or 10% for elevations between 2000 and 4500 feet in Canada. If the heating value
of the gas has ben reduced, these rules do not apply. To identify the proper orifice size, check with the local gas
utility.
If installing this appliance at an elevation above 4500 feet (in Canada), check with local authorities.