Installation manual
630167_5_Manual_Installation_US_R-emotion 
12.0   Installing the Flue System: 
Ensure all flue components are Simpson Duravent Direct Vent Pro 5” x 8,” or a compatible 
equivalent. 
Note: Consult Appendix A at the end of this installation manual (section 24.0) to  
    ensure correct length of flue is calculated. 
  There are two basic types of Balanced Flue System installations: 
  • Horizontal Termination 
  • Vertical Termination 
  Use the diagrams in sections 12.5, 12.6 & 12.7 to check if your proposed flue system is 
acceptable. Section 12.9 will also need to be used to determine whether the flue terminal 
location meets the requirements of ANSI Z21.88-2009 Vented Gas Fireplace Fireplaces. 
Then use Appendix A to work out the quantities of the flue components that are required. 
This gas appliance must not be connected to a chimney flue serving a 
separate solid-fuel burning appliance 
12.1  Any offsets in your flue configuration should be 45° where possible.  
12.2  If your flue configuration has a horizontal run, there must be a minimum 1° inclination (3/4” 
vertical rise per 3‟ horizontal run) leading upwards towards the termination. 
  Do not install the flue with horizontal sections sloping down towards the termination. 
This could cause the fireplace to operate incorrectly and possibly create an unsafe 
condition. 
12.3  The flue must maintain the following  
  clearances to combustible materials; 
  1” from all sides and bottom of 
  the flue, and 2” from the top of 
  the flue. 
12.4  If your flue configuration falls on or near a restriction zone boundary line in diagrams 12.5, 
12.6 & 12.7, it may require the restriction value from either side of the boundary line to 
achieve the correct flame aesthetic, this may vary from installation to installation. 










