Installation manual
630288_0_Manual_Installation-Service_ST900_AUS NZ
20
12.13 Points to note when planning the Installation of the Escea DV flue:
- This flue system cannot be cut to length. Correct lengths must be selected for each
installation. For a full list of available flue lengths, contact your Escea retailer.
- The listed length of the flue pipe is not the installed length. 1 ½” (38mm) needs to be
subtracted for each join to determine the installed length of each piece of flue pipe.
E.g. 48” length has installed length of 45”.
- All vertical measurements should be measured from the top surface of the fireplace casing
itself (not the fascia).
- When using horizontal flue runs, vertical measurements should be measured to the centre
line of the horizontal flue pipes.
- When using 90° elbows in the installation, use the diagram below to help calculate
installations horizontal and vertical distances. 1½” (38mm) will still need to be subtracted
from each join.
- If using a 45° offset in your installation, consult the chart below to select the required flue
length to give the desired offset. 1½” (38mm) will still need to be subtracted from each of
the 45° bends to allow for the joins.
- Adjustable lengths are available depending on stock levels. Contact escea for more
information.
Straight
Flue Length:
Offset:
Rise:
0”
5
5
/
8
”
15
3
/
8
”
6”
8
7
/
8
”
18
3
/
8
”
9”
10
7
/
8
”
20
5
/
8
”
12”
13”
22
5
/
8
”
24”
21
3
/
8
”
31
1
/
8
”
36”
29
7
/
8
”
39
3
/
8
”
48”
38
1
/
4
”
47
7
/
8
”