Service manual
B
ACD
E F G SERVICE
30
If unable to acheive pressures from table in E8:
Adjust point B (shown in section E8) with a 3mm allen key
to adjust the LOW setting, and a 2mm allen key to adjust the
HIGH setting.
NOTE: Do not use a ball-end allen key. Use only square-
end allen keys for adjusting this point.
Take black cap o the solenoid
Put manometers on points A and C
Adjust point C to acheive Operating Pressure (Post-Regulator) from table in section E8
Put the re into ame eect mode using the remote control
Adjust the LOW setting (ame eect) using 3mm allen key to acheive values from
table in section E8
Turn o ame eect using remote, and turn to high
Check that the HIGH setting is within 0.05kPa of value in table of section E8., and if
not, adjust the HIGH setting using 2mm allen key on point B.
If this does not acheive the correct pressures, do Basic Settings:
Using the 2mm allen key, turn counter-clockwise until resistance
Using the 3mm allen key, turn counter-clockwise until resistance
Using the 3 mm allen key, turn 1 rotation clockwise
Using the 2mm allen key, turn 2 ½ rotations clockwise
Adjust LOW again with 3mm allen key, and check HIGH as per above directions.
E9 Operating the Appliance
Turn on the re by pressing the “ ” power button the remote and within a few seconds
the appliance will begin its startup sequence, with a 15 second purge of the ue fan.
After purge it will arc It may take a few attempts to light the rst time due to air in the gas
line. You may wish to purge the gas line at the valve by bleeding the rst test point. This
requires a small blade screwdriver.
Once the re has lit the pilot and main burner you will be able to measure the operating
pressure. Set the remote temperature to 30deg by pressing the “+” button. This will allow
maximum gas ow into the appliance.
Ensure all other gas appliances within the house are also operating at maximum.
If the operating pressure does not read within 5% of the table above then remove the cap
from the gas pressure regulator within the appliance and adjust the threaded spring stop.
The true adjusted pressure can only be read with the cap replaced.
Press the “
” power button again to shut down the re.