D3 Installing the Horizontal Powerue option
The location of the Horizontal Powerue Wall Terminal must be installed in accordance
with AS/NZS 5601.1 and any other relevant building codes. Avoid installing the Horizontal
Powerue Wall Terminal in areas exposed to high winds and extreme weather, if possible.
D4 Installing in Accordance with Relevant Codes
Some of those minimum clearances for a fan assisted wall terminal are listed below;
please refer to AS/NZS 5601.1 Gas installation standard for full guidance on the design of
the ue system. Where possible allow a greater clearance.
A Below eaves, balconies and other projections 200mm
B From the ground, above a balcony or other surface 300mm
C From a return wall or external corner 300mm
D From a gas meter or regulator vent 1000mm
E From electricity meter or fuse box 500mm
F From a drain pipe or soil pipe 75mm
G Horizontally from any building structure or obstruction 500mm
H From any other ue terminal or combustion air intake 300mm
J Horizontally from any openable window, door, non-mechanical air
inlet, or any other opening into a building with the exception of sub
oor ventilation (or 1500mm in direction of discharge)
300mm
K From a mechanical air inlet or spa blower 1000mm
N Vertically below any openable window, door, non-mechanical air
inlet, or any other opening into a building with the exception of sub
oor ventilation
150mm