Specifications

VCES-ERV-IOM-3B – Indoor ERV
18
Appendix C: Dimensional Drawing
Exhaust fan
access panel
36.500”
[927]
65.000”
[1,651]
68.500”
[1,740]
71.000”
[1,803]
42.500”
[1,080]
2.750”
[70]
2.251”
[57]
22.000”
[559]
12.883”
[327]
42.000”
[1,067]
Cassette, filter
access panel
Optional externally mounted
supply damper for all
Frost Control options, excluding
D – Recirc Defrost
Supply air opening
Exhaust air
opening
Supply fan
control box
access panel
Outdoor air
opening
Return air
opening
8.000”
[203]
20.000”
[508]
1.117”
[28]
8.000”
[203]
1.750”
[44]
20.000”
[508] 2.625”
[67]
22.500”
[572]
0.750”
[19]
18.750”
[476]
12.000”
[305]
8.250”
[210]
7.250”
[184]
12.000”
[305]
8.000”
[203]
8.000”
[203]
7.250”
[184]
1.750”
[44]
20.000”
[508]
37.500”
[953]
40.000”
[1,016]
42.500”
[1,080]
Return air
Outdoor air
Exhaust air
A
C
Supply air
Note: A minimum of 42.000” [1,067] clearance from any obstruction is required
for removal of energy recovery module, fans and filters.
Line power
Junction box
4.750” x 4.750”
[121 x 121]
Energy recovery
module
Filter access panel
PTS
A
B
C
D
TOTAL
LBS
120.95
114.35
136.05
128.65
500.00
Kg
54.87
51.87
61.71
58.35
226.80
ERV1000i
Dimensions in [ ] are millimeters.
Center of gravity
Direction of airflow
Low voltage connection
(leave 16” [406] in front for access)
Notes:
Hanging mount hole Ø 0.625” [16]
Note: If the unit is to be hung, materials
required to hang the unit will be
supplied by others.
FRONT VIEW RIGHT VIEWLEFT VIEW
RIGHT VIEW
TOP VIEW
Figure C1: ERV1000i unit dimensional drawing