Specifications

VCES-ERV-IOM-3B – Indoor ERV
10
Electrical Requirements
Location of wire connections required are shown in Ap-
pendix C.
A junction box or disconnect switch must be field supplied
where line voltage connections are made. Consult the
local building electrical codes for the proper selection of
power disconnect device(s).
A low voltage remote control wiring interface is provided
on the unit. The installer must provide wiring for the con-
trols that may be supplied optionally. The optional wall
controls require a four-wire LVT 24 gauge (or equivalent).
This control is 12 VDC. Other terminals are 24 VAC or dry
contact control. Terminals are available for the following
controls:
Low-Com-High
Makes dry contact for speed setting.
Wall control
Four-wire LVT 24 gauge minimum (12 VDC).
Occupied (or night setback) timer/sensor
Needs dry contact to operate. 24 VAC required
when timer is used. Do not use with Xtra wall
control.
Enthalpy control
24VAC.
Remote fan control
Requires single pole, double throw switch.
Dirty filter sensor
Makes dry contact.
Low temperature control
Makes dry contact.
Wheel rotation sensor
Makes dry contact.
CO
2
ventilation control
Makes dry contact.
Unoccupied recirc contacts
24 VAC.
Smoke detector
Makes dry contact.
For more information on the controls available for the
outdoor energy recovery ventilators, see the following Ap-
pendix E references:
Wall Control Connection
Occupied Timer/Sensor Connection
Enthalpy Control
Remote Fan Control
Dirty Filter Sensor
Wheel Rotation Sensor used as Low Temperature
Control (Wheel Failure)
Wheel Rotation Sensor
CO
2
Ventilation Control
Unoccupied Recirc Contacts
Smoke Detector
Recirculation Defrost
Recirculation defrost is a temperature initiated time based
cycle which will de-energize the exhaust fan and the
wheel drive motor, close the outdoor air damper and
circulate return air through both sides of the wheel. If re-
circulation is in operation, it will run approximately 15%
of the time, only when the outdoor air temperature falls
below 5°F [−15°C]. Please note that if the indoor relative
humidity is expected to be 30% or less, please contact a
Venmar CES representative or use the Venmar Select™
software as frost control may not be required.
Exhaust Only Defrost
Exhaust only defrost is a temperature initiated time-based
cycle which will de-energize the supply fan, close the
outdoor air damper and exhaust return air through the ex-
haust side of the wheel as it continues to rotate. If exhaust
only is in operation, it will run approximately 15% of the
time, only when the outdoor air temperature falls below
5°F [−15°C]. Please note that if the indoor relative humid-
ity is expected to be 30% or less, please contact a Venmar
CES representative or use the Venmar Select software as
frost control may not be required.
Electrical Connections
Start-up
Controls
Frost Control
WARNING
Unit cabinet must have an uninterrupted, unbroken elec-
trical ground to minimize the possibility of personal injury
if an electrical fault should occur. Failure to follow this
warning could result in the installer being liable for per-
sonal injury of others.
!