Datasheet
Catalog E 074441 03/03 Edition 3 www.erni.com 9
ERbic Profibus
Profibus is the most widely used field bus. It is promoted by
Siemens and by organized, interested and committed manu-
facturers and users in the PNO (Profibus user organization).
The IP 20 interface on the device side is standardized as a
9-pin D-Sub female connector. The max. data transmission
rate is 12 Mbit/s. The cable is a shielded twisted pair con-
ductor.
The cable sheath is violet and the signal cores are green (A)
and red (B).
With its comprehensive program, ERNI provides customers
with a wide variety of options.
Particular emphasis should be placed on the different termi-
nation technologies, from the traditional screw terminal to the
cage clamp terminal to the IDC terminal.
Electrical and mechanical characteristics
Interface connector D-Sub, 9-pin, male
Cable termination 2 x horizontal, 2 x vertical, MAX: 2 x axial
1 cable outlet can be sealed with blanking plate
Cable diameter 4.5 mm (0.177”) – 8.0 mm (0.315”)
Cross section of individual conductor Screw terminal: solid max. 1.5 mm2; stranded max. 1.0 mm2
IDC terminal: solid ø 0.64 mm
Cage-clamp terminal: 0.08 - 0.5 mm2 (0.75 mm2)
Termination type Screw terminal, IDC terminal, cage-clamp terminal
Data transmission rate According to bus specification, 12 MBit/s
Temperature range -20 °C – +70 °C
Permissible humidity Max. 75 % at + 25 °C, non-condensing
Protection class IP 40, MAX: IP 30
Housing material Thermoplast UL94V-1, MAX: ZnAl, galvanized
Sub-D screw #4/40 UNC, knurled with cross-head
UL approval UL E84703 *
CE marking ERbic connectors are passive components and do not need
to be identified with the CE marking according to EU direc-
tives.
* Due to continuous advancement, it is possible that the UL approval of a new version may not have been completed at the time of going to
press.
Pin configuration
Terminal D-Sub Pin Signal
B (1) 3 RxD/TxD-P
A (2) 8 RxD/TxD-N
B (3) 3 RxD/TxD-P
A (4) 8 RxD/TxD-N
-5 GND
-6 VP (+5V)