Submittal Sheet

Table Of Contents
F-26496-7 Copyright 2010 Schneider Electric All Rights Reserved. 9
N O T E
Three-way N.O. applications can be achieved when using a N.C. actuator, by piping the
valve in reverse. The three-way examples show normally closed actuators.
Sweat Connections
C A U T I O N
Do not solder with actuator in place, or with paddle against seat, as the heat can damage
the unit. Before soldering, move the manual open lever into Open position then remove the
actuator from the body. Orient paddle so it is not against a seat.
Use lead or tin based solder with melting point below 600 °F. Do not overheat. Direct flame
tip away from valve. Cool valve quickly with a wet cloth.
Body assembly can be submerged for leak testing prior to attaching the actuator.
POWER
OFF
A
B
Coil
POWER
OFF
A
B
Coil
POWER
OFF
A
B
Coil
POWER
OFF
AB
Coil
POWER
OFF
A
B
Coil
A
B
POWER
OFF
Coil
Figure-6b 2-Way Valve With
Normally Open Actuator
Figure-6a 2-Way Valve With
Normally Closed Actuator
Figure-6c 3-Way Valve in
Mixing Configuration Normally
Closed to the Coil
Figure-6d 3-Way Valve in
Mixing Configuration Normally
Open to the Coil
Figure-6e 3-Way Valve in
Diverting Configuration
Normally Closed to the Coil
Figure-6f 3-Way Valve in
Diverting Configuration
Normally Open to the Coil