Submittal Sheet

4 © Copyright 2013 Schneider Electric All Rights Reserved. F-26496-8
Example:
Assembly: VT2213G13A020. Components: VT2213 = Body. AG13A020= Actuator.
The actuator part number is prefixed with the letter "A".
Part Numbering System
Two Position Zone Valves, Spring Return Actuators
V X X X X X X X X X XX X
Voltage
A = 24 VAC, 50/60 HZ
B = 110 VAC, 60 HZ, 120 VAC, 50 HZ
D = 208 VAC, 50/60 HZ
T = 277 VAC, 50/60 HZ
U = 230 VAC, 50 HZ and 240 VAC, 60 HZ
Electrical Leads
00 = 6" Motor Wires
01 = Terminal Block with End Switch
(General Temp., 24 VAC only)
02 = 18" (Standard) Wire Leads
Options
0 = No Options
A = End Switch
Actuator Type
G = On/Off (General Close-Off)
H = On/Off (High Close-off)
No. 2-way 3-way
1 = 1.0 1.5 1/2" 1, 2, 3, 5
3/4" 4
2 = 2.5 3.0 1/2" 1, 2, 3, 5
3/4" 1, 2, 3, 4
1/2" 1, 2, 3, 5
3 = 3.5 4.0 3/4" 1, 2, 3, 4
1" 1
5 = 5.0 5.0 3/4" 1, 2, 3
1" 1
7 = 7.5 7.5 3/4" 1, 2, 3
8.0 8.0 1" 1, 2, 3
1-1/4" 1
Connection Type Availability
1 = Sweat 1/2", 3/4", 1", 1-1/4"
2 = Threaded NPT 1/2", 3/4", 1"
3 = Threaded Rp (metric) 1/2", 3/4", 1"
4 = Inverted Flare (Retrofit) 3/4"
5 = SAE Flare 1/2"
Body Type &
Temperature
T = On/Off (General)
S = On/Off (Steam)
High temperature
actuator must be used.
Configuration
2 = 2-Way
3 = 3-Way
Valve Size
2 = 1/2"
3 = 3/4"
4 = 1"
5= 1-1/4"
Temperature Ratings
3 = General Temperature
4 = High Temperature
Body & Actuator Combination Requirements
Temperature Configurations
Body Configuration
V T X X X X
Actuator Spring Return Mode
A X X 3 X X X X
T = General
S = Steam
If body configuration is T, actuator temp rating can be 3 or 4.
If body configuration is S, actuator temp rating must be 4.
3 = General Temperature
4 = High Temperature
If actuator temp rating is 3, body style must be T.
If actuator temp rating is 4, body style can be S or T.
Size Connection Type
1
2
3
4
1 = Normally Closed 2-way and 3-way
2 = Normally Open 2-way only
Spring Return Availability
5
When ordering valve body only: use the first
six positions to configure the valve.
1
2
Inverted flare fittings must be ordered separately. See
actuator accessories for fitting part numbers.
3
5
End switch is not available for 277 Vac models if
actuator temperature rating is high temperature (4).
4
When ordering actuator only use the last seven positions
to configure the actuator. Prefix with the letter "A".
Actuators with Terminal blocks require endswitch and
the endswitch is 24 Vac @ 101 mA min. -5A max.
6
End switch is 24 - 240Vac @ 101 mA min. to 5 A max. and
9-30 Vdc @ 100 mA max for actautors rated 240V or less.
End switch is 277Vac @ 101 mA min. to 5A max for
actuators rated 277V.
5
6
CV Size