User Guide
F-27013-4 © Copyright 2006 TAC All Rights Reserved. 3
SPECIFICATIONS
Inputs
* Factory supplied. (Actual range is 1-9 Vdc.)
Outputs
Timing:
Mechanical:
Action, T series: Direct acting.
P series: Direct acting (valve opens port B with increase in signal.) Field
selectable reverse acting.
Manual Override, Allows manual positioning.
Operating Pressure Limits, 300 psi (2068.4 kPa) static pressure.
Material,
Actuator: High temperature plastic.
Valve: Body: Forged brass; stem: nickel-plated/chrome-plated brass; seat:
brass, plug/paddle: high temperature thermoplastic/rubber.
Flow Characteristic, 1.0 to 4.0 Cv: equal percentage. 7.0/8.0 Cv: linear.
Series Mode Action VAC Frequency
Control Circuit, Max. Total Actuator, Max.
mA VA mA VA
AT13A00T
Floating
Spring
Return
24 Vac
+25%/-15%
50/60 Hz
24 0.6 68 1.6
AT23A00T 24 0.6 68 1.6
AT33A000
Non- Spring
Return
- - 40 1.0
AT33A00T 60 Hz - - 50 1.2
Series Mode Action VAC Frequency
Control Circuit
Total Actuator,
Max.
Range Rin mA VA
AP13A000
Modulating
Spring
Return
24 Vac
+25%/-15%
50/60 Hz
*0-10 VDC or
0-5 VDC or
5-10 VDC or
4-20 mA
>200K
>200K
>200K
300
65 1.6
AP23A000
AP33A000
Non-Spring
Return
Series Mode Action
Nominal Stroke
Time
Total Run Time
60 Hz 50 Hz 60 Hz 50 Hz
AT13A00T
Floating
Spring
Return
2 min. 30
sec.
3 min.
3 min.
3 min.
36 sec.
AT23A00T
AT33A000
Non-Spring
Return
no delay
AT33A00T
3 min.
± 30 sec.
na
AP13A000
Modulating
Spring
Return
2 min.
45 sec.
3 min.
18 sec.
AP23A000
AP33A000
Non-Spring
Return