The figures for maximum power consumption are a round value and state
maximum power consumption only. Power consumption will be lower for most
traffic scenarios.
1.4.3 Physical Site Requirements
Floor Requirements
The floor should be as close to level as possible. The slope must not exceed
1.5 mm/m. This allows the adjustable feet of the base to compensate for
irregularities.
Shelter Requirements
The RBS 3202 cabinet is designed for “free standing” installation.
Room Requirements
figure 4 and figure 5 show the room requirements for the RBS 3202.
Figure 4 Distances in Earthquake Zone
Figure 5 Distances in Non-earthquake Zone
A minimum of 200 mm must be left between cabinets and cable ladders to
allow air flow to the cabinet.
A 300 mm space between the cable ladder and the ceiling is recommended,
this allows working space during the installation of cables. A distance of 1000
mm is required in front of the cabinets. The cable inlet must be aligned with the
indoor and outdoor cable ladders. The inlet must also allow sufficient space to
handle the installation. Dimensions for the earthquake zone are shown infigure
4. Dimensions for the non-earthquake zone are shown in table 2.
Table 2 Distances in Earthquake Zone and Non-earthquake Zone
Dimension Earthquake Zone Non-earthquake Zone
Cabinet front to wall or
surrounding equipment
1000 mm 1000 mm
Cabinet side or back to
the wall
75 mm
10 mm
Cabinet top to cable
ladder
200 mm 200 mm
Cable ladder to ceiling
300 mm
(recommended)
300 mm
(recommended)