DESCRIPTION 5 ( 12 )
EIN/R/I Maude Andersson 1/1553-COH 109 334/1 Uen
ERA/RGG/THC 2002-05-31 B
Prepared (also subject responsible if other) No
Approved Checked Date Rev Reference
E
RBS 3202 cabinet, fully equipped 200 kg
Base 10 kg
1.3 Standard Configurations
This section provides information about the standard configurations for the
RBS 3202.
The following configurations exist:
• The 1 x 1 configuration has one sector and one carrier.
• The 2 x 1 configuration has two sectors and one carrier.
• The 3 × 1 configuration has three sectors and one carrier.
This configuration has two transmission solutions: ET-M1 and ET-M4.
1.4 External Requirements
This section provides information about external site requirements for the
RBS 3202.
The following requirements are described in this section:
• Grounding requirements (chapter 1.4.1)
• Power requirements (chapter 1.4.2)
• Physical site requirements (chapter 1.4.3)
• Climate control requirements (chapter 1.4.4)
1.4.1 Grounding Requirements
All cabinets are connected to the same grounding point in the equipment
room. For more information about grounding requirements, see
Installation of
Grounding Network (1531-FCM 101 1614)
.
1.4.2 Power Requirements
The power requirement for the RBS 3202 is nominal -48 V DC, with a 150 A
fuse. Operational voltage is between –40.5 V DC and –57.0 V DC.
Table 1 Nominal and Maximum Power Consumption by Configuration
Configuration
Average Power
Consumption
Maximum Power
Consumption
3×1
1.6 kW 2.3 kW