Reference Manual

Product Data RBS 2106
Combined Climate Unit. This has both heating and refrigeration.
Air-to-Air Heat Exchanger climate unit. This provides heating,
and cooling through forced convection. It has no refrigerating
capacity; the cabinet cannot be cooled to a temperature lower than
that of the outside (ambient) air.
Both types consist of a Climate Control Unit (CCU), a heater, a heat
exchanger, fans and air-ducts. The Combined Climate Unit has in
addition a compressor, condenser, evaporator, reducing valve and an
AC-powered condenser fan, to refrigerate the cooling air.
The CCU monitors temperatures both inside and outside the cabinet. It
provides heating or cooling by controlling the heater and fans (internal
and external); in the Combined Climate Unit it also controls the
compressor and the condenser fan. The CCU also performs alarm
handling and test functions.
P008419A
Combined Climate Unit RBS
CCU DC/DC AC/DC
Transformer
Heater
Sub Racks
Return Air
Supply Air
Heat
Exchanger
Condensor Evaporator
Active
Cooler
Figure 33 Block diagram, Combined Climate Unit
EN/LZT 720 0008 P2A
2001-11-28
91 (485)
© Ericsson Radio Systems AB
All Rights Reserved
Preliminary