Reference Manual

Unit Description, ACCU-02
Table 128 AC supply 60 Hz
Single-phase, three-wire, earthed
mid-point
200/100 V AC to 240/120 V AC
Three-phase star, four-wire
1)
, earthed
neutral
208/120 V AC to 220/127 V AC
1)
It is also possible to supply the ACCU with a three-phase, five-wire
system (separate neutral and earth conductors).
Table 129 Priority DC supply to control unit
Option Voltage Range Max. Current
+24 V DC +18 to +32 V DC
1A
2)
-48 V DC -39 to -60 V DC
0.6 A
2)
2)
mA excluding internal lightning.
17.4.2 Output Data
Table 130 Output voltages
PSU 1 - 4 180 - 275 V AC
Climate Unit 180 - 275 V AC
Service Outlet Same as input (line to neutral)
Internal lightning +24 V DC
+18 to +32 V DC
Auxiliary +24 V DC +18 to +32 V DC
Note: The DC output voltages require DC input voltage.
Table 131 Output power
PSU 1 - 4
1500 W each
Climate Unit
3000 W
Service Outlet 1500 W (50 Hz), 1200 W (60 Hz)
Internal lightning +24 V DC
1A
Auxiliary +24 V DC
1A
17.5 Technical Data
17.5.1 Distribution Unit
Table 132 Dimensions
Width 435 mm (excluding mounting bracket)
Height 149 mm
Depth
250 mm
202 (485)
EN/LZT 720 0008 P2A
2001-11-28
© Ericsson Radio Systems AB
All Rights Reserved
Preliminary