Reference Manual

Unit Description, ACCU-02
One outlet for Climate Unit, protected by a 25 A circuit breaker
One Service outlet, protected by a 10 A circuit breaker with
residual current breaker
Two DC outputs for cabinet lighting and auxiliary equipment,
protected by 1 A circuit breakers
Rectifier for supply of Control Unit
Voltage Regulator for supply of Control Unit and DC outputs
from +24 or -48 V DC
Relays which provide possibility to turn on and off the PSU
outputs
Control Unit
17.2 Functions
Distributes AC power to the PSUs and makes it possible to
connect and disconnect the PSUs through the EPC bus.
Distributes AC power to the Climate Unit.
Provides EMC-filtering and protection against power line
disturbances on the incoming AC power.
Acts as a Disconnecting Device (Main Switch).
Supervises the mains and gives an alarm on undervoltage, fuse
fault and worn out overvoltage protectors.
Provides +24 V DC outputs to lighting in the cabinet and to
auxiliary equipment.
Provides a Service Outlet for instruments and tools.
17.3 Indicators
Table 126 ACCU indicators
Indicator
Colour
Operational Green
Control board fault Yellow
EPC bus fault
Yellow
Varistor fault Yellow
200 (485)
EN/LZT 720 0008 P2A
2001-11-28
© Ericsson Radio Systems AB
All Rights Reserved
Preliminary