Reference Manual

Product Data RBS 2206
Site Equipment Room
P006362A
a
2
=130
o
1000
800
1000
Unit of measurement: mm
300
250
Figure 50 Floor layout and space requirements
The picture above shows floor layout and space requirements.
There must always be a space between the cabinet and the cable ladder
for the flow of exhaust air, and to be able to replace fans.
If the RBS cabinet must meet earthquake requirements, the space
between wall and cabinet must be at least 100 mm, and between
cabinets at least 150 mm.
6.4.3 Weights
Table 60 Weight of cabinet
Unit Weight
Fully equipped cabinet incl. base
frame
230 kg
Base frame 12 kg
The weight of the heaviest replaceable unit is less than 15 kg (CDU-G).
118 (485)
EN/LZT 720 0008 P2A
2001-11-28
© Ericsson Radio Systems AB
All Rights Reserved
Preliminary