equipment and/or the DC/DC converter until the voltage has
dropped to 20.0 V DC.
The temperature of the batteries is too high.
A short circuit occurs between the distribution cables. This will
release the circuit breaker in the BFU.
The BFU also supplies voltage through two fuses directly to
transmission equipment and/or through the DC/DC converter (optional)
to transmission equipment. BFU-21 supplies through two fuses (12 A),
BFU-22 supplies through one fuse (40 A).
One BFU is needed for each RBS cabinet.
BFU-21 and BFU-22 differ in their power outputs, see Table 53 on
page 95.
DC/DC converter (optional)
The DC/DC converter is located in the BBS and converts +24 V DC
to -48 V DC.
Battery Blocks
The batteries are for stationary use. They are a sealed lead-acid type,
with valve ventilators. The battery is composed of battery blocks in one
or more battery strings. One string of +24 V batteries has four 6 V
blocks.
Further information regarding the BBS 2000 can be found in:
Power Manual BBS 2000 K 1556-BZZ 208 06-101
5.6.5 Cable Connection Interfaces
See Section 5.3.2 +24 V DC Power Supply on page 82.
5.7 Antenna System
This chapter contains information about antenna congurations for
outdoor cells.
There are a number of antenna system products available, such as
antennas, feeders, jumpers, TMAs and so on. For more detailed
information about products, see
RBS Site Solutions homepage:
http://gsmrbs.ericsson.se/gsmsystems/solutions/rbs_site_solutions/
index.htm