User's Manual Part 3
RBS 2308 and RBS 2309 User’s Guide
If the yellow Local indicator is flashing and the anticipated BSC communication
cannot be established, then perform the following actions step-by-step (in close
cooperation with the BSC operator) until the fault ceases:
•ResettheIXU
• Ensure that the expected Transmission OK indicators are on
Note: Transmission OK indicators only indicate that the incoming
transmission signal is present electrically. The physical
transmission connection should still be checked.
• Ensure that the TEI value in the RBS IDB corresponds with the CF TEI value
set in the BSC for this RBS. Request that the BSC operator checks that no
other RBSs are using the s ame CF TEI value on the transmission line
• If a PSTU is used, ensure that the PSTU is in operation (otherwise, follow
the instructions in the PSTU Alarm OPI, Ethernet Interface Down) and that
the transmission interface parameter in the RBS IDB is set to IP
• If a PSTU is not used, ensure that the following transmission parameters
in the RBS IDB are correct:
− Transmission interface
− CRC-4
− Spare bits
− Synchronization source
− Receiver sensitivity
− LBO
• Ensure that all RBSs, connected on the same transmission line between the
BSC and this RBS, have Cascade defined as Network Topology in the IDB
• Ensure that the BSC has a correctly configured A-bis path to the RBS
• Ensure that the c orresponding TRH and RBLT devices in the BSC are
working
RBS Fault
If the yellow RBS Fault indicator is on, an RBS fault is detected. Perform the
following actions step-by-step until the fault ceases:
• Use the OMT to display fault information, see Section 10.3 Fault
Localization Using OMT on page 176
1
97
EN
/LZT 720 0027 Uen R8A 2006-06-27