User Manual
Table Of Contents
- toc
- RBS Product Description
- 1 Introduction
- 2 Product Overview
- 3 Dimensions
- 4 Space Requirements
- 5 Environment
- 6 Hardware Units
- 7 Interfaces
- 8 Power System
- 9 Transmission
- 10 External Alarms
- 11 Standards, Regulations and Dependability
- RBS Product Description
- tables
- Table 1 Weights
- Table 2 Colour
- Table 3 Environmental Specifications
- Table 4 Compliance Boundary Dimensions for the General Public (G
- Table 5 Characteristics for a Typical Antenna (KRE 101 1916/1)
- Table 6 Maximum Power to Antenna for Various RBS Configurations
- Table 7 RBS 2206 External Connections
- Table 8 RBS 2206 V2 External Connections
- Table 9 AC Power Requirements
- Table 10 Fuse Specifications
- Table 11 Fuse Specifications
- Table 12 +24 V DC Power Requirements
- Table 13 Fuse Specifications
- Table 14 Fuse Specifications
- Table 15 Requirements
- Table 16 Fuse Specifications
- Table 17 Fuse Specifications
- Table 18 Power Consumption RBS 2206
- Table 19 Power Consumption RBS 2206 V2
Ericsson Internal
DESCRIPTION 7 ( 34 )
/ XSNSIXI 19/1551-LZA 701 0001 Uen
CBC/ XRX/M ( Kai Lian) 2011-05-05 G
Prepared (also subject responsible if other) No.
Approved Checked Date Rev Reference
Space above the RBS Cabinet
P006382A
1770
2070
250
400
600
300
1820
Figure 1 Cabinet Dimensions
The recommended distance between the cabinet and cable ladder is 250 mm.
A shorter distance makes it difficult to exchange fans and may restrict the air
flow. A space of 300 mm is recommended above the cable ladder to make
cable installation work easier.
RBS 2206:
Depth of cabinet including door is 470 mm, of which the door is 70 mm.
RBS 2206 V2: